TD ADDENDUM SECTION 1. FUNCTIONAL MODES
AD-1-4
to which memory is cleared on powerup, to set
the PakBus ID, and to set communication to full
or half duplex.
CSI datalogger support software makes use of the
∗D Mode to upload and download pr
ograms from a
computer. Appendix C gives some additional
information on Commands 1 and 2 that are used
for these operations.
When "∗D
" is keyed in, the CR10X will display
"13:00". A c
ommand (Table 1.8-1) is entered
by keying the command number and "A".
TABLE 1.8-1. ∗D Mode
Commands
Command Description
1 Send (Print) ASCII Program
2 Load ASCII Program, ∗0 Compile
2-- Load ASCII Program, ∗6 Compile
3 # Rings Before Answering Phone
7 Erase Current Program
10 Set Powerup Options
12 Set Initial Baud
15 PakBus Address/Routing Table
16 Memory for General Purpose File
17 PakBus Routing Table
18 PakBus Beacon Interval
19 PakBus Neighbor List
If the CR10X program has not been compiled
when the command to save a program is entered,
it will be compiled before the program is saved.
When a program is loaded, it is immediately
compiled and run. When a command is complete,
"13:0000" is displayed; ∗D must be entered again
before another command can be given.
TABLE 1.8-2. Program Load Error Codes
E 94 Program Storage Area full
E 95 Program does not exist in flash
E 96 Storage Module not connected or
w
r
ong address
E 97 Data not encountered within 30 sec.
E 98 Uncorrectable errors detected
E 99 Wrong type of file or Editor Error
1.8.1 ERASING CURRENT PROGRAM
The 7 command may be used to delete the
cur
rent program as show in Table 1.8-3.
TABLE 1.8-3 Deleting Current Datalogger
Program
Key entry Display
∗D 13:00
7A
07:00
You may now enter:
0A Erase active program (i.e., load a
blank pr
ogram; memory allocation
and Final Storage are reset).
1.8.2 PROGRAM TRANSFER WITH STORAGE
MODULE
Not supported in Table Data Operating
Sy
stems.
1.8.3 FULL/HALF DUPLEX
Not supported in Table Data Operating
S
y
stems.
1.8.4 SET DATALOGGER ID
Command 8 not supported in Table Data
O
per
ating Systems.
1.8.5 SETTING POWERUP OPTIONS
Setting options for the Program on Powerup
allow
s
the user to specify what information to
retain from when the datalogger was last on.
This allows Flag/Port status, the User Timer,
and the Input/Intermediate Storage to be
cleared or not cleared.
Table 1.8-8. Setting Powerup Options
Key entry Display
∗D 13:00
10A
10:0X
Where X is the powerup option currently
selec
ted. You may now change the option:
0A Clears input locations, ports, flags, user
timer
, and intermediate storage locations.
1A Clears intermediate storage only (leaves
Input Stor
age, F
lags/Ports, and User Timer
as is).
2A Doesn’t clear anything.