Appendix B. Example Programs
B.2.2 Edlog Differential Measurement Program
Below is an example CR10X program. Information about using it with other
Edlog dataloggers are provided in the program’s comments.
;Turn the HMP155A on.
;
01: Do (P86)
1: 41 Set Port 1 High ;Jumper wire from SW12V control to C1
;Green wire (C1) if using SW12V device
;For CR23X or CR5000 use 49 for SW12V internal
;control port
;Pause 2 seconds before making measurements so the
;probe can stabilize on true readings.
;
02: Excitation with Delay (P22)
1: 1 Ex Channel
2: 0 Delay W/Ex (units = 0.01 sec)
3: 500 Delay After Ex (units = 0.01 sec)
4: 0 mV Excitation
;Measure the HMP155A temperature.
;
03: Volt (Diff) (P2)
1: 1 Reps
2: 5 2500 mV Slow Range ;CR510, CR500 (2500mv); CR23X (1000 mV);
21X, CR7 (5000 mV)
3: 2 DIFF Channel ;Yellow wire (2H), jumper (2L to 1L)
4: 1 Loc [ T_C ]
5: .14 Mult ;See TABLE 7-4 for alternative multipliers
6: -80 Offset ;See TABLE 7-4 for alternative offsets
;Measure the HMP155A relative humidity.
;
04: Volt (Diff) (P2)
1: 1 Reps
2: 5 2500 mV Slow Range ;CR510, CR500 (2500mv); CR23X (1000 mV);
21X, CR7 (5000 mV)
3: 1 DIFF Channel ;Blue wire (1H), white or purple wire (1L)
4: 2 Loc [ RH_pct ]
5: .1 Mult ;See TABLE 7-5 for alternative multipliers
6: 0 Offset
;Turn the HMP155A off.
;
05: Do (P86)
1: 51 Set Port 1 Low ;Jumper wire from SW12V control to C1
;Green wire (C1) if using SW12V device
;For CR23X or CR5000 use 59 for SW12V internal
;control port